Manufacturer of Rechargeable Led Emergency Driver - LED Emergency Driver Lasting 3 Hours – SASELUX
Manufacturer of Rechargeable Led Emergency Driver - LED Emergency Driver Lasting 3 Hours – SASELUX Detail:
- This emergency kit provides
60-180 Minutes duration in the event of a power failure. Suit for LED luminaire with external driver 100W or below.
- Lithium iron phosphate Battery backup
IFR18650MUB 3.2V 1500mAh battery cell,
- Output: DC10-50V. 50-200V Constant power 2-6W
Dimension
-Automatic self-test function
-Status of the battery.
-Status of the LED
-Charge condition
-Duration test
-Functional test
Application
-LED Downlight, Tri-proof, Linear LED light fixture
Battery pack
There are three combinations of batteries. Please ask the service commissioner for the specifications.
Model |
Output Constant power |
Battery backup |
Duration |
CK-7091L | DC 10-50V 6W |
LiFePO4 6.4V 1.5AH |
1 hour |
CK-7091H | DC 50-200V 6W |
LiFePO4 6.4V 1.5AH |
1 hour |
CK-7092L | DC 10-50V 3W |
LiFePO4 6.4V 1.5AH |
2 hours |
CK-7092H | DC 50-200V 3W |
LiFePO4 6.4V 1.5AH |
2 hours |
CK-7093L | DC 10-50V 4W |
LiFePO4 6.4V 1.5AH |
1.5 hours |
CK-7093H | DC 50-200V 4W |
LiFePO4 6.4V 1.5AH |
1.5 hours |
CK-7094L | DC 10-50V 2W |
LiFePO4 6.4V 1.5AH |
3 hours |
CK-7094H | DC 50-200V 2W |
LiFePO4 6.4V 1.5AH |
3 hours |
CK-7095L | DC 10-50V 4W |
LiFePO4 6.4V 3.0AH |
3 hours |
CK-7095H | DC 50-200V 4W |
LiFePO4 6.4V 3.0AH |
3 hours |
Automatic self-test function
LED status display
Functional test
Connecting battery firstly, connecting mains supply then, this emergency conversion module will automatically go into emergency mode and discharge for 3 seconds.
Timer stats to calculate when battery is fully charged for the very first time.
The emergency conversion module will automatically discharge 10 seconds every 30 days as a short time functional test.
Duration test
Emergency conversion module will automatically discharge 90 minutes every 180 days.
If a mains supply failure occurs at any time, before or during functional test and duration test period, emergency conversion module will go into emergency mode immediately. Timer would not re-calculate if battery is not disconnected after emergency mode. If the battery is disconnected, timer will re-calculate.
The test switch and indicator light are connected through a plug on the inverter.
Product detail pictures:
Related Product Guide:
We also offer you product sourcing and flight consolidation expert services. We've our personal manufacturing unit and sourcing business. We can offer you virtually every variety of merchandise associated to our item range for Manufacturer of Rechargeable Led Emergency Driver - LED Emergency Driver Lasting 3 Hours – SASELUX , The product will supply to all over the world, such as: Myanmar, Angola, Jamaica, We will supply much better products with diversified designs and professional services. We sincerely welcome friends from over the world to visit our company and cooperate with us on the basis of long-term and mutual benefits.